7.10 Digital Inputs And Outputs In Transient Recorder Mode
7.10.1 Start IN/ExTrig
This input can be used to start the digitisation with a high or low (select in Ext CSR) going edge.
The signal comes in to the unit via the rear transition card see appendix B.
7.10.2 Start Out
The Start IN digitisation signal is gated to Start OUT to allow a single start signal to trigger multiple
units. The signal comes in to the unit via the rear transition card see appendix B. This output can be
configured to be either high or low TTL signal level (select in TR CSR).
7.10.3 Stop IN
This stops the unit digitising, the unit can be triggered again once this signal is removed. This signal is
ORed with the software stop bit in the TR CSR. The external Stop IN signal comes in to the unit via the
rear transition card see appendix B. This input can be configured to except either a high or low TTL
signal level (select in TR CSR).
If the unit is stopped by either the software stop or the External stop bit when the stop bit is released the
pre-trigger delay will be indicated.
7.10.4 Stop Out
This feeds the Stop signal to the out to the rear transition card (see appendix B). This output can be
configured to be either high or low TTL signal level (select in TR CSR).
7.10.5 Clock In
This allows an external sample clock to be used up to 1MHz. The signal comes in to the unit via the rear
transition card see appendix B.
7.10.6 Clock Out
This allows the internal sample clock (as set by ADC Sample Rate Reg at 6hex) to be feed out to the rear
transition card (see appendix B).